Modbus/TCP~

The Modbus connector allows to read and write entities using the Modbus/TCP protocol. See Settings on how to enable and configure the Modbus connector.

EMS Entity / Modbus Register Mapping~

This document refers to the device issuing a Modbus request as the client (formerly known as a Modbus master) and to the device listening and fulfilling the requests, i.e. EMS-ESP, as the server (formerly known as a Modbus slave).

EMS-ESP creates a Modbus server for each device connected to the EMS bus, including EMS-ESP itself. Each server is addressed with a numeric identifier representing the device type. See Server Unit Identifiers for a list of all possible server IDs.

A server organizes all entities of the device it represents in blocks that correspond to the entity tags (e.g. hc1 for the first heating circuit). The entities are addressed with an offset within the register block. See Register Blocks for a list of all block offsets.

All values are stored in one or more registers.

  • Each Modbus register contains a 16 bit value.
  • Numeric values are stored as 16 or 32 bit integers, in one or two registers. An entity specific scale factor may be applied. The scale factor is defined separately for each device and entity.
  • Enums are stored in a single register.
  • Strings are null terminated and stored with two characters per register.

See Entity/Register Mapping for a list of all register offsets, data types and scale factors.

Example

A Modbus client wants to read the target flow temperature of the second heating circuit (hc2) of a thermostat of type RC310 connected to the EMS bus.

  • Table Server IDs indicates that the unit identifier of a thermostat device is 6. So the client needs to specify the unit identifier 6 in all requests.
  • Table Register Blocks shows that the offset for HC2 is 2000.
  • The row targetflowtemp in table Entity/Register Mapping for thermostat RC310 lists register offset 18, register count 1 and scale factor 1. Hint: click a column header to sort the table, e.g. by entity shortnames.

So the final register offset for the target flow temperature in hc2 is 2000 + 18 = 2018. We need to read one register at offset 2018 from the server with unit ID 6 and multiply the result by the scale factor which in this case is 1.

The SYSTEM server~

EMS-ESP assigns a special unit identifier, 1, to a server that provides general information about EMS-ESP. The system server registers are documented here.

Reading and Writing Entity values~

The following Modbus function codes are implemented:

  • READ_HOLD_REGISTER (0x03)
  • READ_INPUT_REGISTER (0x04)
  • WRITE_HOLD_REGISTER (0x06)
  • WRITE_MULT_REGISTERS (0x10)

The Modbus connector supports reading and writing of a single entity per request. Reading or writing multiple entities, even if mapped to consecutive registers, is not supported. However, a single entity that is mapped to multiple registers must be read or written in a single request.